Refrigerant leak inspection
Term · Environment · MLC-T-ENV-023554
Examination of an appliance to determine the location of refrigerant leaks. Potential methods include, but are not limited to, ultrasonic tests, gas-imaging cameras, bubble tests as appropriate, or the use of a leak detection device operated and maintained according to manufacturer guidelines. Methods that determine whether the appliance is leaking refrigerant but not the location of a leak, such as standing pressure/vacuum decay tests, sight glass checks, viewing receiver levels, pressure checks, and charging charts, must be used in conjunction with methods that can determine the location of a leak.
| Identifier | MLC-T-ENV-023554 |
|---|---|
| Field | Environment |
| Subject | Commercial processes |
| References | 40 CFR 82.152 (CFR 2017) |