Interrupting time

Term · Industrial and trades · MLC-T-IND-003062

The time a circuit breaker needs to interrupt current, measured from the moment its trip coil is energized until the arc is extinguished in all poles. It is the sum of the mechanism's opening time and the arcing time, and it excludes relay detection time, so the total clearing time from fault inception is longer. Ratings are stated in cycles of the power frequency, as in 3-cycle and 5-cycle breakers.